4.12 Control parameters
For the monitoring of the system bus and the display of the internal states, two con-
trol parameters are provided. There is a report of the system bus state and a report o
f
the CAN state via two actual value parameters.
The parameter
Node-State 978 gives information about the Pre-Operational, Opera-
tional, Stopped state. A PDO transfer is only possible in the Operational state. The
state is controlled by the system bus master (PLC / PC / frequency inverter) via NM
T
telegrams.
The parameter
CAN-State 979 gives information about the state of the physical layer.
If there are transmission errors, the state chan
g
es from OKAY to WARNING until the
cancellation of the communication with BUS-OFF. After BUS-OFF, the CAN controller is
automatically re-initialized and the system bus started again.
Note: If the BUS-OFF state occurs, the frequency inverter breaks down with
"F2210 BUS-OFF".
After Bus-OFF, the system bus in the frequency inverter is completely reinitialized.
There is a new boot-up message from the node and an emergency telegram with the
Bus-OFF messa
g
e is transmitted. The chan
g
e of state of the node to Operational is
done by the Start-Remote-Node telegram cyclically sent by the system bus master.
Actual values of the system bus
No. Description Function
978 Node-State 1 - Pre-Operational
2 - Operational
3 - Stopped
979 CAN-State 1 - OKAY
2 - WARNING
3 - BUS-OFF