4.7.1 SDO channels (parameter data)
Each frequency inverter possesses two SDO channels for the exchan
e of paramete
data. In a slave device, these are two server SDO's, in a device defined as a master a
client SDO and a server SDO. Attention must be paid to the fact that only one maste
for each SDO channel may exist in a system.
Note: Only one master can initiate by the system bus an exchan
e of data via
its client SDO.
The identifier assignment for the SDO channels (Rx/Tx) is done according to the Pre-
defined Connection Set.
This assignment can be amended by parameterization, in order to solve identifier con-
flicts in a lar
er system in which further devices are on the CAN bus alon
side the
frequency inverters.
Attention! In a system in which a frequency inverter works as a master, the identi-
fier allocations for the SDO channel may not be altered.
In this way, an addressin
of individual nodes via the field bus/system
bus path of the master frequency inverter is possible.
Parameters are read/written via the SDO channels. With the limitation to the SDO
Se
ment Protocol Expedited, which minimizes the handlin
needed for the parameter
exchan
e, the transmittable data are limited to the uint / int / lon
types. This permits
complete parameterization of the frequency inverters via the system bus, as all the
settings and practically all the actual values are displayed via these data types.
4.7.2 PDO channels (process data)
Each frequency inverter possesses three PDO channels (Rx/Tx) for the exchan
e o
process data.
he identifier assi
nment for the PDO channel (Rx/Tx) is done by default accordin
to
the Predefined Connection Set. This assi
nment corresponds to an ali
nment to a
central master control.
In order to produce the logical channels between the devices (transverse movement)
on the system bus, the amendment of the PDO identifiers for Rx/Tx is necessary.
Each PDO channel can be operated with time or SYNC control. In this way, the opera-
tion behavior can be set for each PDO channel:
The setting of the operation mode is done via the following parameters:
TxPDO1 Function 930, TxPDO2 Function 932 und TxPDO3 Function 934
RxPDO1 Function 936, RxPDO2 Function 937 und RxPDO3 Function 938
Operation mode Function
0 -deactivated no exchange of data via the PDO channel (Rx and/or Tx)
1 -time-controlled Tx-PDO’s cyclically transmit according to the time specifica-
tion
Rx-PDO‘s are read in with Ta = 1 ms and forward the data
received to the application
2 -SYNC controlled Tx-PDO’s transmit the data from the application that are
then current after the arrival of the SYNC telegram.
Rx-PDO’s forward the last data received to the application
after the arrival of the SYNC telegram.
For synchronous PDO’s, the master (PC, PLC or frequency inverter)
enerates the
SYNC tele
ram. The identifier assi
nment for the SYNC tele
ram is done by default
accordin
to the Predefined Connection Set. This assi
nment can be altered by
parameterization.